shutdown is required every 24 hours. The LAE10 is designed for the supervision of oil flames in connection with selenium photocell detectors RAR... Flame safeguards are used primarily in conjunction with the LEC1 burner control on the following applications:
- Dual-supervision of burners: Supervision of the main flame or of the pilot and main flame by two identical or different types of flame detectors
- Supervision of forced draught oil / gas burners: Supervision of the flame with different types of detectors, depending on the operating mode
- Multi-flame supervision: Plants with several burners whose flames must be supervised individually by one or several detectors, whose startup and supervision, however, should or must be carried out centrally and simultaneously by only one burner control
- The flame safeguards can also be used in connection with other types of burner controls provided the given combination and selected circuitry do not impair the burner control’s safety functions
- The flame safeguards are also used as flame indication units in combustion plant with manual startup
技術參數
主要參數 |
主電壓 |
AC220V -15%...AC240V +10% |
AC100V -15%...AC1100V +10% |
主頻率 |
50...60Hz ±6% |
外部保險絲 |
10A |
功率 |
4.5VA |
端口額定電流 |
2A |
保護等級 |
IP40 |
重量(不含底座) |
305g |
|
環境條件 |
運輸環境 |
IEC 60 721-3-2 |
內部條件 |
class 2K2 |
機械條件 |
class 2M2 |
溫度范圍 |
-20...+60ºC |
濕度 |
<95% |
運行環境 |
IEC 60 721-3-3 |
內部條件 |
class 3K5 |
機械條件 |
class 3M2 |
溫度范圍 |
-20...+60ºC |
濕度 |
<95% |